Stamford Alternator 60kVA Generator set
Basic Info
Model No.: HPG65 lovol 1004TG
Product Description
Stamford Alternator 60kva Generator Set
Stamford Alternator 60kVA Generator set specifications as follows PERKINS 1004 SERIES DATA SHEET
Generator set | Generating Model | HPM65 |
Rating Power (KW/KVA) | 48/60 | |
Standby Power(KW/KVA) | 52/65 | |
rating Ammeter(A) | 87 | |
| Engine Model | 1004TG |
Prime Power(KW) | 66 | |
Standby Power(KW) | 74 | |
Bore X Stroke (mm) | 100X127 | |
number of Cylinder & Configuration | 4 in line | |
Displacement (l) | 3.99 | |
Compression Ratio | 16 | |
Aspiration Type | Turbocharged | |
Max. intake depression(kPa) | 0.85 | |
Combustion air Volume(m³/min) | 4.7 | |
Max. Exhaust back Pressure (kPa) | 5 | |
Exhaust Gas Flow(m³/min) | 14.0 | |
Max. Exhaust Gas Temperature | 596 | |
Cooling Type | Water cooled with Radiator | |
Fan cooling air flow(m³/min) | 160 | |
Total Coolant capacity(l) | 18.7 | |
Max. temperature of coolant | 103 | |
Max. permissible oil temp. | 105 | |
Total oil capacity(l) | 8.1 | |
Rating Fuel Consumption(l/h) | 18.6 | |
Governing Type | Mechanical Governor | |
Alternator | Rating Voltage(V) | 400/230 |
Alternator Model | MP-48-4 | |
Rating Capacity(KW/KVA) | 58/72.5 | |
Eff.% | 85.6% | |
Power Factor | 0.8 lagged | |
Exciting type | Brushless self-exciter, AVR | |
Voltage regulation | ±1% | |
No. of Phase | 3 phase 4 wire | |
Enclosure Class | IP21 | |
Class of Insulation | H | |
Control Panel | Control Module UK DEEP SEA | GCS6410 AMF Module |
Battery | Rating Capacity(AH) | 2X100AH 12V |
Dimension | Generator set dimension (LXWXH)(mm) | 2150X750X1400 |
Weight | Weight (kg) | 870 |
Product Categories : 10-100KVA Generator